Parâmetro Valor
GTIN 4017918164027
Orderkey 2818850
Catalog page Page 475 (C-8-2013)
Packing unit 1 pc
Note (General) To meet the discharge conditions for DC voltages, please note the following information: "The surge protective device should be used together with a transmitter unit, which shuts down in the event of a short-circuit."
Country of origin DE (Germany)
(Connection data) EN 61643-21 2001 + A1:2009
Custom tariff number 85363010
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) Attachment plug
(Additional descriptions) D1 - 2.5 kA
Depth (Key Commercial Data) 67 mm
Width (Key Commercial Data) 25 mm
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Height (Key Commercial Data) 25 mm
Degree of protection (Dimensions) IP55
Capacity (Additional descriptions) typ. 1.5 pF
Mounting type (Ambient conditions) Connection-specific intermediate plugging
Weight per Piece (excluding packing) 131.450 g
Housing material (Ambient conditions) Nickel-plated brass
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Connection method (Protective circuit) N connector 50 Ω
Rated current (Additional descriptions) 5 A (25 °C)
Degree of pollution (Ambient conditions) 2
Direction of action (Ambient conditions) Line-Shield/Earth Ground
Connection method IN (Protective circuit) N connector, female
Overvoltage category (Ambient conditions) III
Connection method OUT (Protective circuit) N connector, female
Response time tA (Additional descriptions) ≤ 100 ns
Standards/specifications (Connection data) IEC 61643-21 2000 + A1:2008
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC test classification (Additional descriptions) C1
Input attenuation aE, asym. (Additional descriptions) typ. 0.1 dB (≤ 1.2 GHz / 50 Ω)
Maximum continuous voltage UC (Additional descriptions) 280 V DC
Surge protection fault message (Additional descriptions) none
Impulse durability (line-earth) (Additional descriptions) C1 - 1 kV/500 A
Impulse durability (line-shield) (Additional descriptions) C1 - 1 kV/500 A
Operating effective current ICat UC (Additional descriptions) ≤ 1 µA
Voltage protection level Up(line-earth) (Additional descriptions) ≤ 900 V (C1 - 1 kV/500 A)
Total discharge current Itotal(8/20) µs (Additional descriptions) 20 kA
Voltage protection level Up(line-shield) (Additional descriptions) ≤ 900 V (C1 - 1 kV/500 A)
Standing wave ratio SWR in a 50 Ω system (Additional descriptions) typ. 1.1 (≤ 2 GHz)
Nominal discharge current In(8/20) µs (line-earth) (Additional descriptions) 20 kA
Nominal discharge current In(8/20) µs (line-shield) (Additional descriptions) 20 kA
Nominal pulse current Ian (10/1000) µs (line-earth) (Additional descriptions) 100 A
Nominal pulse current Ian (10/1000) µs (Core-Shield) (Additional descriptions) 100 A
Permissible HF power Pmaxat VSWR = xx (50 ohm system) (Additional descriptions) 700 W (VSWR = 1.1)
Pulse discharge current Iimp(10/350) µs (line-earth) (Additional descriptions) 2.5 kA
Pulse discharge current Iimp(10/350) µs (line-shield) (Additional descriptions) 2.5 kA
Output voltage limitation at 1 kV/µs (line-earth) spike (Additional descriptions) ≤ 900 V
Output voltage limitation at 1 kV/µs (line-shield) spike (Additional descriptions) ≤ 900 V
Max. discharge current Imax(8/20) µs maximum (line-earth) (Additional descriptions) 20 kA
Max. discharge current Imax(8/20) µs maximum (line-shield) (Additional descriptions) 20 kA
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system (Additional descriptions) > 3 GHz

Descrição do produto

Replaceable surge protection adapter for coaxial signal interfaces. Connection: N Female Connector
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top