Especificações principais
GTIN: 4055626725222
Orderkey: 1064922
(Drawings):
Catalog page: Page 262 (C-4-2019)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4055626725222
Orderkey 1064922
(Drawings)
Catalog page Page 262 (C-4-2019)
Depth (Note) 159 mm
Packing unit 1
Width (Note) 36 mm
(Input data) < 0.1 % (change in input voltage ±10 %)
Height (Note) 160 mm
(Output data) > 620000 h (60 °C)
ETIM 5.0 (eCl@ss) EC002540
ETIM 6.0 (eCl@ss) EC002540
ETIM 7.0 (eCl@ss) EC002540
Custom tariff number 85044030
(Ambient conditions) typ. 20 ms (500 V AC)
Derating (Input data) > 60 °C ... 70 °C (2.5%/K)
REACh SVHC (EMC data) Lead 7439-92-1
(Conformance/approvals) 2 kV (Test Level 1 - asymmetrical)
Efficiency (Output data) typ. 91 % (400 V AC)
Net weight (Output data) 0.7 kg
UL approvals (Standards) UL Listed UL 61010-2-201
Output power (Input data) 120 W
Climatic class (Dimensions) 3K3 (in acc. with EN 60721)
Connection method (General) Snap-on connection
Residual ripple (Input data) ≤ 20 mVPP
eCl@ss 6.0 (Classifications) 27049000
eCl@ss 7.0 (Classifications) 27049002
eCl@ss 8.0 (Classifications) 27049002
eCl@ss 9.0 (Classifications) 27040701
Input (Conformance/approvals) 3 kV (Test Level 3 - symmetrical)
Control deviation (Input data) < 1 % (change in load, static 10 % ... 90 %)
Output (Conformance/approvals) 1 kV (Test Level 2 - symmetrical)
Protection class (Output data) II (in closed control cabinet)
Signal (Conformance/approvals) 1 kV (Test Level 1 - symmetrical)
Input fuse (Ambient conditions) 3.15 A (internal (device protection), slow-blow)
Voltage (Conformance/approvals) 230 V AC
Comments (Conformance/approvals) Criterion A
Degree of pollution (Dimensions) 2
Installation height (Dimensions) ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Connection in series (Input data) yes
Degree of protection (Dimensions) IP20
Frequency (Conformance/approvals) 50 Hz
Degree of protection (Output data) IP20
Typical response time (Input data) < 1 s
Utilization restriction (Drawings) EMC: class A product, see manufacturer's declaration in the download area
Assembly instructions (Output data) Cross Power System
Connection in parallel (Input data) Yes, for redundancy and increased capacity
Criterion A (Conformance/approvals) Normal operating behavior within the specified limits.
Criterion B (Conformance/approvals) Temporary impairment to operational behavior that is corrected by the device itself.
Inrush current (Ambient conditions) ≤ 22 A (typical)
Nominal output voltage (Input data) 24 V DC ±1 %
Voltage dip (Conformance/approvals) 0 %
Voltage dips (Conformance/approvals) EN 61000-4-11
Noise emission (Conformance/approvals) EN 55016
AC frequency range (Ambient conditions) 50 Hz ... 60 Hz
Additional text (Conformance/approvals) Test Level 2
Dynamic Boost (IDyn.Boost) (Input data) 7.5 A (5 s)
Frequency range (Conformance/approvals) 2 GHz ... 3 GHz
Type of protection (Ambient conditions) Transient surge protection
Current consumption (Ambient conditions) 3x 0.4 A (400 V AC)
Discharge in air (Conformance/approvals) 8 kV (Test Level 4)
Input voltage range (Ambient conditions) 3x 400 V AC ... 500 V AC -20 % ....+15 %
MTBF (IEC 61709, SN 29500) (Output data) > 2300000 h (25 °C)
Nominal output current (IN) (Input data) 5 A
Contact discharge (Conformance/approvals) 6 kV (Test Level 4)
Mains buffering time (Ambient conditions) typ. 20 ms (400 V AC)
Number of periods (Conformance/approvals) 1 period
Power loss nominal load max. (Input data) < 12 W (480 V AC)
Stripping length (Connection data, input) 10 mm
Connection method (Connection data, input) Push-in connection
Stripping length (Connection data, output) 8 mm
Connection method (Connection data, output) Push-in connection
Power factor (cos phi) (Ambient conditions) 0.55
Test field strength (Conformance/approvals) 10 V/m (Test Level 3)
Ambient temperature (operation) (Dimensions) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Discharge current to PE (Ambient conditions) < 0.25 mA
Insulation voltage input/output (Output data) 3 kV AC (type test)
Low Voltage Directive (Conformance/approvals) Conformance with Low Voltage Directive 2014/35/EC
Nominal power consumption (Ambient conditions) 243.6 VA
Electrostatic discharge (Conformance/approvals) EN 61000-4-2
Fast transients (burst) (Conformance/approvals) EN 61000-4-4
Conducted noise emission (Conformance/approvals) EN 55016
Electromagnetic HF field (Conformance/approvals) EN 61000-4-3
Nominal input voltage range (Ambient conditions) 3x 400 V AC ... 500 V AC
Protective circuit/component (Ambient conditions) Varistor
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Electromagnetic compatibility (Conformance/approvals) Conformance with EMC Directive 2014/30/EU
Setting range of the output voltage (USet) (Input data) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Conductor cross section AWG max. (Connection data, input) 12
Conductor cross section AWG min. (Connection data, input) 24
Standard - Safe isolation (Connection data for signaling) DIN VDE 0100-410
Conductor cross section AWG max. (Connection data, output) 16
Conductor cross section AWG min. (Connection data, output) 24
Conductor cross section solid max. (Connection data, input) 4 mm²
Conductor cross section solid min. (Connection data, input) 0.2 mm²
Max. permissible relative humidity (operation) (Dimensions) ≤ 95 % (at 25 °C, non-condensing)
Maximum power dissipation in no-load condition (Input data) < 1 W (400 V AC)
Conductor cross section solid max. (Connection data, output) 1.5 mm²
Conductor cross section solid min. (Connection data, output) 0.2 mm²
Standard - Electrical safety (Connection data for signaling) IEC 61010-1 (SELV)
Recommended breaker for input protection (Ambient conditions) 6 A ... 16 A (AC: Characteristics B, C, D, K)
Conductor cross section flexible max. (Connection data, input) 2.5 mm²
Conductor cross section flexible min. (Connection data, input) 0.2 mm²
Conductor cross section flexible max. (Connection data, output) 1.5 mm²
Conductor cross section flexible min. (Connection data, output) 0.2 mm²
Protection against overvoltage at the output (OVP) (Input data) ≤ 30 V DC
Standard - Safety of transformers (Connection data for signaling) EN 61558-2-16 (air clearances and creepage distances only)
EMC requirements for noise immunity (Connection data for signaling) EN 61000-6-2
Standard – Safety extra-low voltage (Connection data for signaling) IEC 61010 (SELV) / (PELV)
Standard – Limitation of mains harmonic currents (Connection data for signaling) EN 61000-3-2
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) EN 50178/VDE 0160 (PELV)

Descrição do produto

Primary switching power supplies, TRIO POWER, Snap-on connection, Cross Power System: mounting, input:3phase, output: 24 VDC / 5 A
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Detalhes técnicos

Block diagram

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top