Parâmetro Valor
Surge protection
Note Device supply and 8 x inputs
Depth 82.5 mm
Width 50 mm
Height 48.5 mm
General For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.
Data rate 19200 Baud
Insulation Basic insulation
Product type Base unit
Buffer period 96 h (Capacitor)
Input voltage 24 V DC
Mounting type Plug-in mounting
Operating mode 100% operating factor
Product family PLC logic
Realtime clock Yes
Status display Yellow LED
Supply voltage 24 V DC
Nominal current 9 mA
Input resistance > 3.5 kΩ
Number of inputs 8 (2 configurable as analog)
Pollution degree 2
Stripping length 9 mm
Connection method Push-in connection
Cross section AWG (converted acc. to IEC)
Mounting position any
Number of outputs ≤ 8
Protective circuit Reverse polarity protection
Dimensional drawing
Input voltage range 0 V ... 10 V
Number of positions 10
Protocols supported Modbus/RTU
Rated surge voltage 0.8 kV
Degree of protection IP20
Overvoltage category III
Supply voltage range 19.2 V DC ... 26.4 V DC
Termination resistor 150 Ω
Assembly instructions can be plugged onto 8 x PLC-INTERFACE terminal blocks
Number of connections 1
Standards/regulations DIN EN 50178
Nominal output voltage 24 V DC
Accuracy realtime clock ±2 s/d
Signal level "0" signal < 5 V
Signal level "1" signal > 11 V
Description of the input EN 61131-2, type 3
Input current "0" signal < 1 mA
Input current "1" signal 2.5 mA
Rated insulation voltage 50 V
Conductor cross section AWG 26 ... 16
Maximum input current at UN 160 mA
Typical current consumption 4 mA
Typical input current at UN 40 mA
Conductor cross section rigid 0.14 mm² ... 1.5 mm²
Ambient temperature (operation) -20 °C ... 50 °C
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Ambient temperature (storage/transport) -20 °C ... 70 °C
Max. permissible relative humidity (operation) 95 %

Descrição do produto

PLC logic expansion module with 16 I/Os for plug-in connection to 8 PLC-INTERFACE terminals for expansion of the basic module (maximum 2 expansion modules can be connected to one basic module),
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top