Horário de atendimento: Segunda a sexta, das 9h às 18h.
PLT-SEC-T3-60-FM-PT - PLT-SEC-T3-60-FM-PT 2907926 PHOENIX CONTACT Type 3 surge protection device
Em estoque Produto em alta

PLT-SEC-T3-60-FM-PT

PLT-SEC-T3-60-FM-PT 2907926 PHOENIX CONTACT Type 3 surge protection device

$0.00 USD
4310 em estoque
Especificações principais
GTIN: 4055626257624
Orderkey: 2907926
(General): ≤ 8.4 mVA (at UC)
Packing unit: 5 pc
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4055626257624
Orderkey 2907926
(General) ≤ 8.4 mVA (at UC)
Packing unit 5 pc
(Dimensions) ≤ 6000 m (operating voltage remote contact ≤ 150 V)
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85363030
(Ambient conditions) PA 6.6-FR
(Protective circuit) (DC+/DC-) - PE
Altitude (Dimensions) ≤ 2000 m (operating voltage remote contact ≤ 250 V)
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) light gray RAL 7035
Depth (Key Commercial Data) 74.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data) 17.7 mm
(Additional technical data) 0.5 A DC (75 V DC)
EN type (Ambient conditions) T3
Height (Key Commercial Data) 101 mm
Nominal voltage UN (General) 60 V AC (TN-S)
Combination wave UOC (General) 4 kV
Nominal frequency fN (General) 50 Hz (60 Hz)
Residual current IPE (General) ≤ 5 µA
Shock (operation) (Dimensions) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General) 26 A (at 30 °C)
Response time tA(L-N) (General) ≤ 25 ns
Response time tA(L-PE) (General) ≤ 100 ns
Response time tA(N-PE) (General) ≤ 100 ns
Degree of protection (Dimensions) IP20
TOV behavior at UT(L-N) (General) 120 V AC (120 min / withstand mode)
Mounting type (Ambient conditions) DIN rail: 35 mm
TOV behavior at UT(L-PE) (General) 120 V AC (120 min / withstand mode)
Vibration (operation) (Dimensions) 5g (5 ... 500 Hz / 2.5 h / X, Y, Z)
Number of ports (Ambient conditions) One
Weight per Piece (excluding packing) 77.160 g
Housing material (Ambient conditions) PA 6.6-FR 20% GF
Reference test voltage UREF (General) 66 V AC
Horizontal pitch (Key Commercial Data) 1 Div.
Standby power consumption PC (General) ≤ 5.3 mVA (at UREF)
Maximum continuous voltage UC (General) 80 V AC
Mode of protection (Ambient conditions) L-N
Mode of protection (Protective circuit) (DC+) - (DC-)
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 2
Standards/specifications (Connection data) IEC 61643-11 2011
Voltage protection level Up(L-N) (General) ≤ 0.48 kV
Voltage protection level Up(L-PE) (General) ≤ 0.8 kV
Voltage protection level Up(N-PE) (General) ≤ 0.8 kV
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TN-S
Short-circuit current rating ISCCR (General) 10 kA AC
Stripping length (Additional technical data) 10 mm
Connection method (Additional technical data) Push-in connection
Max. backup fuse with branch wiring (General) 32 A (gG / B / C)
Operating current (Additional technical data) 0.5 A AC
Operating voltage (Additional technical data) 250 V AC
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 10 mm
Connection method (Indicator/remote signaling) Push-in connection
Switching function (Additional technical data) PDT contact
Maximum backup fuse for through wiring (General) 25 A (gG / B / C)
Nominal discharge current In(8/20) µs (General) 2 kA
Maximum continuous voltage UC (Protective circuit) 80 V DC
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Conductor cross section AWG (Additional technical data) 30 ... 12
Short-circuit current rating ISCCR (Protective circuit) 0.25 kA DC (without additional backup fuse)
Conductor cross section AWG (Indicator/remote signaling) 24 ... 12
Conductor cross section solid (Additional technical data) 0.2 mm² ... 2.5 mm²
Conductor cross section solid (Indicator/remote signaling) 0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section flexible (Additional technical data) 0.2 mm² ... 2.5 mm²
Conductor cross section flexible (Indicator/remote signaling) 0.2 mm² ... 2.5 mm²
Maximum discharge current Imax(8/20) µs (Protective circuit) 4 kA

Descrição do produto

Type 3 surge protection, consisting of plug-in protection and base element, with integrated status indicator and remote indication for single-phase power supply networks. Rated Voltage: 60VAC/DC
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top