Horário de atendimento: Segunda a sexta, das 9h às 18h.
PT 2+1-S-48DC/FM - PT 2+1-S-48DC/FM 2817958 PHOENIX CONTACT Type 3 surge protection device
Em estoque Produto em alta

PT 2+1-S-48DC/FM

PT 2+1-S-48DC/FM 2817958 PHOENIX CONTACT Type 3 surge protection device

$0.00 USD
3600 em estoque
Especificações principais
GTIN: 4017918574987
Orderkey: 2817958
(General): 6 kV (12 Ω)
Catalog page: Page 72 (C-4-2017)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4017918574987
Orderkey 2817958
(General) 6 kV (12 Ω)
Catalog page Page 72 (C-4-2017)
Packing unit 10 pc
Country of origin DE (Germany)
(Connection data) IEC 61643-11 2011
Custom tariff number 85363090
(Ambient conditions) (L+/L-) - PE
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) jet black RAL 9005
Depth (Key Commercial Data) 65.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data) 17.7 mm
EN type (Ambient conditions) T3
Height (Key Commercial Data) 90 mm
Nominal voltage UN (General) 48 V DC
Combination wave UOC (General) 1 kV (2 Ω)
Residual current IPE (General) ≤ 10 µA
Rated load current IL (General) 26 A (30 °C)
Response time tA(L-N) (General) ≤ 1 ns
Response time tA(L-PE) (General) ≤ 1 ns
Degree of protection (Dimensions) IP20
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) DIN rail: 35 mm
Number of ports (Ambient conditions) One
Weight per Piece (excluding packing) 63.460 g
Housing material (Ambient conditions) PA 6.6
Stripping length (Protective circuit) 8 mm
Voltage protection level Up (General) ≤ 120 V
Connection method (Protective circuit) Screw connection
Horizontal pitch (Key Commercial Data) 1 Div.
Operating current (Protective circuit) 5 mA DC ... 15 mA (open collector)
Operating voltage (Protective circuit) 7 V DC ... 70 V DC (open collector)
Tightening torque (Protective circuit) 0.8 Nm
Maximum continuous voltage UC (General) 60 V DC
Mode of protection (Ambient conditions) L-N
Switching function (Protective circuit) N/C contact
Degree of pollution (Ambient conditions) 2
Screw thread (Indicator/remote signaling) M3
Standards/specifications (Connection data) EN 61643-11 2012
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
Short-circuit current rating ISCCR (General) 200 A (without backup fuse for Uc)
Max. backup fuse with branch wiring (General) 50 A (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 8 mm
Connection method (Indicator/remote signaling) Screw connection
Tightening torque (Indicator/remote signaling) 0.8 Nm
Conductor cross section AWG (Protective circuit) 24 ... 12
Maximum backup fuse for through wiring (General) 25 A (gG)
Nominal discharge current In(8/20) µs (General) 500 A
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Conductor cross section AWG (Indicator/remote signaling) 24 ... 12
Conductor cross section solid (Indicator/remote signaling) 0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section flexible (Indicator/remote signaling) 0.2 mm² ... 2.5 mm²

Descrição do produto

Surge arrester for rail mounting as device protection for terminal equipment, fault signal on the connector and warning contact on the two-piece, plug-in base element. Execution: 48 V DC
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação