Especificações principais
: C2
Note: Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type: DIN rail module, two-section, divisible
Depth: 77.5 mm (incl. DIN rail 7.5 mm)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
C2
Note Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type DIN rail module, two-section, divisible
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Width 17.7 mm
Height 109.3 mm
Altitude ≤ 4000 m (amsl)
Product type Surge protection for MCR technology
Mounting type DIN rail: 35 mm
Rated current 700 mA (50 °C)
Product family PLUGTRAB IQ
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Connection method Push-in connection
Nominal voltage UN 12 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Resistance per path 1.2 Ω ±5 %
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 1 mA (per path)
IEC test classification C1
Standards/specifications IEC 61643-21
Max. required back-up fuse 800 mA (FF)
Conductor cross section AWG 24 ... 12
Input attenuation aE, asym. typ. 0.3 dB (≤ 130 kHz/150 Ω)
Capacity (line-signalground) typ. 4 nF
Response time tA(line-earth) ≤ 1 ns
Conductor cross section rigid 0.5 mm² ... 4 mm²
Maximum continuous voltage UC 15 V DC
Pulse reset time (line-earth) ≤ 15 ms
Surge protection fault message Optical, multi-stage
Ambient temperature (operation) -40 °C ... 70 °C
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Operating effective current ICat UC ≤ 1 mA (per path)
Flammability rating according to UL 94 V-0
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 90 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 20 kA
Voltage protection level Upstatic (line-earth) ≤ 45 V (C1 - 1 kV / 500 A)
Nominal discharge current In(8/20) µs (line-ground) 10 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 2.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 600 kHz

Descrição do produto

Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for four signal wires with common reference potential. Can be used in safet