Horário de atendimento: Segunda a sexta, das 9h às 18h.
STEP-PS/277AC/24DC/3.5 - STEP-PS/277AC/24DC/3.5 2904945 PHOENIX CONTACT Power supply unit
Em estoque Produto em alta

STEP-PS/277AC/24DC/3.5

STEP-PS/277AC/24DC/3.5 2904945 PHOENIX CONTACT Power supply unit

$0.00 USD
4755 em estoque
Especificações principais
: 95 V DC ... 250 V DC
Depth: 61 mm
Input: 4 kV (Test Level 4 - asymmetrical)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
95 V DC ... 250 V DC
Depth 61 mm
Input 4 kV (Test Level 4 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 90 mm
Height 90 mm
Output 2 kV (Test Level 3 - asymmetrical)
Voltage 3 V (Test Level 2)
Comments Criterion B
Derating 55 °C ... 70 °C (2.5 %/K)
Rise time < 0.5 s (UOUT(10 % ... 90 %))
Efficiency > 88 % (for 277 V AC and nominal values)
Input fuse 4 A (slow-blow, internal)
Output power 84 W
Product type Power supply
Screw thread M3
UL approvals UL/C-UL listed UL 508
Assembly note alignable: 0 mm horizontally, 30 mm vertically
Mounting type DIN rail mounting
Climatic class 3K3 (in acc. with EN 60721)
Inrush current < 40 A (typical)
Product family STEP POWER
Status display "DC OK" LED green
Frequency range 80 MHz ... 1 GHz
Residual ripple < 10 mVPP(20 MHz)
Article revision 02
Discharge in air 8 kV (Test Level 3)
Horizontal pitch 5 Div.
Housing material Plastic
Number of phases 1.00
Protection class II
Stripping length 6.5 mm
Connection method Screw connection
Contact discharge 6 kV (Test Level 3)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Mounting position horizontal DIN rail NS 35, EN 60715
Rail applications EN 50121-4
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Types of signaling LED
Current consumption 1.43 A (120 V AC)
Degree of pollution 2
Foot latch material POM (Polyoxymethylene)
Input voltage range 85 V AC ... 305 V AC
Output current Imax 6 A
Test field strength 10 V/m
Connection in series yes
Degree of protection IP20
Mains buffering time typ. 25 ms (120 V AC)
Overvoltage category III
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Output characteristic U/I
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Typical response time < 0.5 s
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Input voltage range AC 85 V AC ... 305 V AC
Input voltage range DC 95 V DC ... 250 V DC
Nominal output voltage 24 V DC ±1 %
Note on status display UOUT> 21.5 V: LED lights up
Power factor (cos phi) 0.64
Tightening torque, min 0.5 Nm
Permissible backup fuse B6 B10 B16
With protective coating no
Nominal power consumption 147.7 VA
Operating voltage display Green LED
Standard - Safe isolation DIN VDE 0100-410
MTBF (IEC 61709, SN 29500) > 1094000 h (40 °C)
Feedback voltage resistance ≤ 35 V DC
Nominal input voltage range 100 V AC ... 277 V AC
Nominal output current (IN) 3.5 A (-25 °C ... 55 °C)
Power loss nominal load max. 11.5 W
Standard - Electrical safety IEC 62368-1 (SELV)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) < 2.8 A2s
Voltage type of supply voltage AC/DC
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Insulation voltage input/output 4 kV AC (type test)
Conductor cross section AWG max. 12
Conductor cross section AWG min. 24
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm
SIL in accordance with IEC 61508 0
Maximum no-load power dissipation < 0.6 W
Standard - Safety of transformers EN 61558-2-16
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Peak switching voltages nominal load < 30 mVPP(20 MHz)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Setting range of the output voltage (USet) 22.5 V DC ... 25 V DC (> 24 V DC, constant capacity restricted)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Protection against overvoltage at the output (OVP) < 35 V DC
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)

Descrição do produto

Power supply. Carr. system, 24 V DC/3.5 A, primary switched, monof.
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top