Horário de atendimento: Segunda a sexta, das 9h às 18h.
STEP-PS/48AC/24DC/0.5 - STEP-PS/48AC/24DC/0.5 2868716 PHOENIX CONTACT Power supply unit
Em estoque Produto em alta

STEP-PS/48AC/24DC/0.5

STEP-PS/48AC/24DC/0.5 2868716 PHOENIX CONTACT Power supply unit

$0.00 USD
3529 em estoque
Especificações principais
: 60 V DC ... 80 V DC
Depth: 61 mm
Input: 2 kV (Test Level 3 - asymmetrical)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
60 V DC ... 80 V DC
Depth 61 mm
Input 2 kV (Test Level 3 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 18 mm
Height 90 mm
Output 2 kV (Test Level 3 - asymmetrical)
Voltage 10 V
Comments Criterion A
Derating 55 °C ... 70 °C (2.5 %/K)
Efficiency > 81 % (for 48 V AC and nominal values)
Input fuse 1.25 A (slow-blow, internal)
Input/Output Test Level 3
Output power 12 W
Product type Power supply
Screw thread M3
UL approvals UL/C-UL listed UL 508
Assembly note alignable: 0 mm horizontally, 30 mm vertically
Mounting type DIN rail mounting
Climatic class 3K3 (in acc. with EN 60721)
Inrush current < 10 A (typical)
Product family STEP POWER
Status display "DC OK" LED green
Frequency range 80 MHz ... 3 GHz
Residual ripple < 30 mVPP(20 MHz)
Article revision 03
Discharge in air 8 kV (Test Level 3)
Horizontal pitch 1 Div.
Housing material Plastic
Number of phases 1.00
Protection class II (in closed control cabinet)
Stripping length 6.5 mm
Connection method Screw connection
Contact discharge 6 kV (Test Level 3)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Mounting position horizontal DIN rail NS 35, EN 60715
Rail applications EN 50121-4
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Types of signaling LED
Current consumption 0.5 A (43 V AC)
Degree of pollution 2
Foot latch material POM (Polyoxymethylene)
Input voltage range 43 V AC ... 52 V AC
Output current Imax 1 A
Test field strength 10 V/m (Test Level 3)
Connection in series yes
Degree of protection IP20
Mains buffering time typ. 15 ms (48 V AC)
Overvoltage category III
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Output characteristic U/I
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Typical response time < 0.5 s
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallel yes, for redundancy and increased capacity
Input voltage range AC 43 V AC ... 52 V AC
Input voltage range DC 60 V DC ... 80 V DC
Nominal output voltage 24 V DC
Note on status display UOUT> 21.5 V: LED lights up
Power factor (cos phi) 0.7
Tightening torque, min 0.5 Nm
With protective coating no
Nominal power consumption 21 VA
Operating voltage display Green LED
Standard - Safe isolation DIN VDE 0100-410
MTBF (IEC 61709, SN 29500) > 1860000 h (40 °C)
Feedback voltage resistance ≤ 35 V DC
Nominal input voltage range 48 V AC
Nominal output current (IN) 0.5 A (-25 °C ... 55 °C)
Power loss nominal load max. < 3.4 W
Standard - Electrical safety IEC 62368-1 (SELV)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) < 0.1 A2s
Voltage type of supply voltage AC/DC
Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Insulation voltage input/output 4 kV AC (type test)
Conductor cross section AWG max. 12
Conductor cross section AWG min. 24
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm
SIL in accordance with IEC 61508 0
Maximum no-load power dissipation < 0.3 W
Standard - Safety of transformers EN 61558-2-16
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Peak switching voltages nominal load < 20 mVPP(20 MHz)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Protection against overvoltage at the output (OVP) < 35 V DC
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)

Descrição do produto

STEP POWER primary switching power supply for rail mounting, input: single-phase, output: 24 V DC/0.5 A
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top