Horário de atendimento: Segunda a sexta, das 9h às 18h.
STEP3-PS/1AC/5DC/3/PT/USB-A - STEP3-PS/1AC/5DC/3/PT/USB-A 1335699 PHOENIX CONTACT Primary Switching Power Supplies, STEPPOWER, Push-in Con..
Em estoque Produto em alta

STEP3-PS/1AC/5DC/3/PT/USB-A

STEP3-PS/1AC/5DC/3/PT/USB-A 1335699 PHOENIX CONTACT Primary Switching Power Supplies, STEPPOWER, Push-in Con..

$53.87 USD
227 em estoque
Especificações principais
: 230 V AC
Depth: 61 mm
Input: asymmetrical 2 kV (Test Level 3)
Width: 18 mm
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
230 V AC
Depth 61 mm
Input asymmetrical 2 kV (Test Level 3)
Width 18 mm
rigid 0.2 mm² ... 2.5 mm²
Height 90 mm
Output asymmetrical 2 kV (Test Level 3)
Voltage 10 V (Test Level 3)
Comments Criterion A
Derating > 50 °C ... 70 °C (2 % / K)
Position 1.x
flexible 0.2 mm² ... 2.5 mm²
Frequency 50 Hz
Rise time typ. 100 ms (UOut= 10 % ... 90 %)
EN 61010-1 II (≤ 4000 m)
EN 62477-1 III (≤ 2000 m)
Efficiency > 81.5 % (120 V AC)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Voltage dip 70 %
rigid (AWG) 24 ... 14 (Cu)
Crest factor typ. 3.3
Input/Output asymmetrical
Product type Power supply
Mounting type DIN rail or direct mounting
No-load proof yes
Identification UL 1310 Class 2 Power Units
Inrush current typ. 30 A (25 °C)
Noise emission EN 55016
Noise immunity Immunity in accordance with EN 61000-6-2 (industrial)
Product family STEP POWER
Switch-on time typ. 2 s
Additional text Class 3
Frequency range 0 kHz ... 2 kHz
Residual ripple typ. 80 mVPP
Discharge in air 8 kV (Test Level 3)
Horizontal pitch 1 Div. (DIN 43880)
Housing material Plastic
Maximum altitude ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Number of phases 1.00
Position marking 1.1, 1.2 (L), 1.3, 1.4 (N)
Protection class II (in closed control cabinet)
Signal threshold > 0.9 x UN(UN= 5 V DC) (LED lights up green)
Stripping length 10 mm (rigid/flexible/ferrule without plastic sleeve)
Connection method Push-in connection
Contact discharge 6 kV (Test Level 3)
Control deviation < 1.5 % (Static load change 10 % ... 90 %)
Device mains fuse 1.25 A internal (device protection), slow-blow
Mounting position horizontal DIN rail NS 35, EN 60715
Number of periods 25 periods
Output power (PN) 15 W
Shock (operation) 18 ms, 30g, per spatial direction (IEC 60068-2-27)
Types of signaling LED
Current consumption 0.3 A (100 V AC)
Degree of pollution 2
Dimensional drawing
Foot latch material Polyamid
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Short-circuit-proof yes
Test field strength 10 V/m (Test Level 3)
Connection in series yes, for increased output voltage
Degree of protection IP20
Frequency range (fN) 50 Hz ... 60 Hz ±10 %
Mains buffering time typ. 18 ms (120 V AC)
Standard designation Electrical safety
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standards/regulations EN 61000-3-2
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6)
Connection in parallel yes, for increasing power and redundancy with diode
Nominal output voltage 5 V DC
Discharge current to PE < 0.25 mA
With protective coating No
Conducted noise emission EN 55016
Standards/specifications IEC 61010-1 (SELV)
MTBF (IEC 61709, SN 29500) > 2428000 h (25 °C)
Feedback voltage resistance ≤ 10 V DC
Nominal output current (IN) 3 A
Supply system configuration Star network (TN, TT, IT (PE))
Power loss nominal load max. < 3.4 W (230 V AC)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) typ. 0.14 A2s
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Ambient temperature (operation) -10 °C ... 70 °C (Derating: > 50 °C; 2 %/K)
Insulation voltage input/output 4 kV AC (type test)
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm
Maximum no-load power dissipation < 0.1 W (230 V AC)
Minimum no-load power dissipation < 0.1 W (120 V AC)
Environmental protection directive RoHS Directive 2011/65/EU
Flammability rating according to UL 94 V0 (Housing, terminal blocks, base latches)
Minimum nominal load power dissipation < 3.5 W (120 V AC)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
flexible with ferrule with plastic sleeve 0.2 mm² ... 1 mm²
Ambient temperature (start-up type tested) -25 °C
flexible with ferrule without plastic sleeve 0.5 mm² ... 1.5 mm²
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Protection against overvoltage at the output (OVP) < 10 V DC

Descrição do produto

Primary-switched power supply unit, STEP POWER, Push-in connection, DIN rail or direct mounting, Integrated cable groove with strain relief, input: 1-phase, output: 5 V DC / 3 A, USB-A up to 15 W
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top