Horário de atendimento: Segunda a sexta, das 9h às 18h.
TT-2-PE-110AC - TT-2-PE-110AC 2858483 PHOENIX CONTACT Surge protection device
Em estoque Produto em alta

TT-2-PE-110AC

TT-2-PE-110AC 2858483 PHOENIX CONTACT Surge protection device

$0.00 USD
4687 em estoque
Especificações principais
GTIN: 4017918893156
Orderkey: 2858483
(General): D1 - 500 A
Catalog page: Page 94 (C-6-2015)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4017918893156
Orderkey 2858483
(General) D1 - 500 A
Catalog page Page 94 (C-6-2015)
Packing unit 10 pc
Country of origin DE (Germany)
(Connection data) EN 61643-21/A1 2009
Custom tariff number 85363010
Altitude (Dimensions) ≤ 2000 m
Rated current (General) 300 mA (30 °C)
Type (Ambient conditions) Double-level terminal block with PE foot – separate PE connection
Color (Ambient conditions) black
Depth (Key Commercial Data) 54.6 mm
Width (Key Commercial Data) 6.2 mm
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Height (Key Commercial Data) 79.6 mm
Nominal voltage UN (General) 110 V AC
Capacity (line-line) (General) typ. 600 pF
Residual current IPE (General) ≤ 10 µA
Resistance in series (General) 9.4 Ω 10 %
Capacity (line-earth) (General) ≤ 2 pF
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) DIN rail: 35 mm
Input attenuation aE, sym. (General) typ. 1.5 dB (≤ 2 MHz)
Max. required back-up fuse (General) 315 mA (T/IEC 60127-2/3)
Weight per Piece (excluding packing) 26.470 g
Housing material (Ambient conditions) PA 6.6
Input attenuation aE, asym. (General)
Response time tA(line-line) (General) ≤ 1 ns
Stripping length (Protective circuit) 8 mm
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Connection method (Protective circuit) Screw connection
Response time tA(line-earth) (General) ≤ 100 ns
Tightening torque (Protective circuit) 0.8 Nm
Maximum continuous voltage UC (General) 120 V AC
Standards/regulations (Connection data) IEC 61643-21
Direction of action (Ambient conditions) Line-Line & Line-Earth Ground
Impulse durability (line-line) (General) C1 - 1 kV/500 A
Number of positions (Ambient conditions) 2
Surge protection fault message (General) none
Connection method IN (Protective circuit) Screw terminal blocks
Impulse durability (line-earth) (General) C1 - 1 kV/500 A
Connection method OUT (Protective circuit) Screw terminal blocks
Standards/specifications (Connection data) IEC 61643-21/A1 2008
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Operating effective current ICat UC (General) ≤ 5 µA
Conductor cross section AWG (Protective circuit) 24 ... 14
Voltage protection level Up(line-line) (General) ≤ 300 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth) (General) ≤ 900 V (C2 - 10 kV / 5 kA)
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Pulse discharge current Iimp(10/350) µs (General) 500 A
Total discharge current Itotal(8/20) µs (General) 10 kA
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Alternating current carrying capacity (line-line) (General) 0.1 A/1 s
Flammability rating according to UL 94 (Ambient conditions) V-0
Alternating current carrying capacity (line-earth) (General) 1 A/1s
Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) typ. 15 MHz
Nominal discharge current In(8/20) µs (line-line) (General) 5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) typ. 8 MHz
Nominal discharge current In(8/20) µs (line-earth) (General) 5 kA
Nominal pulse current Ian (10/1000) µs (line-earth) (General) 100 A
Output voltage limitation at 1 kV/µs (line-line) spike (General) ≤ 250 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 650 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General) 5 kA
Standards for cearances and creepage distances (Ambient conditions) IEC 60664-1
Max. discharge current Imax(8/20) µs maximum (line-earth) (General) 5 kA

Descrição do produto

Two-level overvoltage-protected terminal block for a two-wire circuit with free operation of ground potential, separate PE connection, nominal voltage: 110 V AC, NS 35/7.5 mounting, terminal width: 6.
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top