Horário de atendimento: Segunda a sexta, das 9h às 18h.
VAL-MS/2+0-BE/FM/S2 - VAL-MS/2+0-BE/FM/S2 2800246 PHOENIX CONTACT Type 2 surge protection base element
Em estoque Produto em alta

VAL-MS/2+0-BE/FM/S2

VAL-MS/2+0-BE/FM/S2 2800246 PHOENIX CONTACT Type 2 surge protection base element

$0.00 USD
3535 em estoque
Especificações principais
GTIN: 4046356519250
Note: Made to Order (non-returnable)
Orderkey: 2800246
Catalog page: Page 50 (C-6-2013)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4046356519250
Note Made to Order (non-returnable)
Orderkey 2800246
Catalog page Page 50 (C-6-2013)
Packing unit 1 pc
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85366990
(Ambient conditions) T2
(Protective circuit) 1 A DC
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) Base element, DIN rail mounting
Color (Ambient conditions) jet black RAL 9005
Depth (Key Commercial Data) 51.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data) 35.6 mm
EN type (Ambient conditions) T2
Height (Key Commercial Data) 96.8 mm
(Indicator/remote signaling) 4.5 Nm (25 mm² ... 35 mm²)
Nominal frequency fN (General) 50 Hz (60 Hz)
Shock (operation) (Dimensions) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General) 80 A
Degree of protection (Dimensions) IP20 (only when all terminal points are used)
Screw thread (Protective circuit) M2
Mounting type (Ambient conditions) DIN rail: 35 mm
Vibration (operation) (Dimensions) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Weight per Piece (excluding packing) 152.250 g
Housing material (Ambient conditions) PBT
Stripping length (Protective circuit) 7 mm
Connection method (Protective circuit) Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data) 2 Div.
Operating current (Protective circuit) 5 mA AC ... 1.5 A AC
Operating voltage (Protective circuit) 5 V AC ... 250 V AC
Tightening torque (Protective circuit) 0.25 Nm
Maximum continuous voltage UC (General) 500 V AC
Standards/regulations (Connection data) IEC 61643-11 2011
Switching function (Protective circuit) PDT contact
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 2
Screw thread (Indicator/remote signaling) M5
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC test classification (Ambient conditions) II
Short-circuit current rating ISCCR (General) 25 kA
Max. backup fuse with branch wiring (General) 200 A (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 16 mm
Connection method (Indicator/remote signaling) Fork-type cable lug
Tightening torque (Indicator/remote signaling) 3 Nm (1,5 mm² ... 16 mm²)
Conductor cross section AWG (Protective circuit) 28 ... 16
Conductor cross section solid (Protective circuit) 0.14 mm² ... 1.5 mm²
Surge protection fault message (Ambient conditions) Remote indication contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Conductor cross section flexible (Protective circuit) 0.14 mm² ... 1.5 mm²
Max. backup fuse with V-type through wiring (General) 80 A (gG)
Conductor cross section AWG (Indicator/remote signaling) 15 ... 2
Conductor cross section solid (Indicator/remote signaling) 1.5 mm² ... 35 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section flexible (Indicator/remote signaling) 1.5 mm² ... 16 mm²

Descrição do produto

Base element downloaded. Type 2 Prods Series. VALVETRAB MS, contact remote indication. Execution for two-phase power supplies with common reference potential.
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top